YBM box substation-European box transformer
Product characteristics
- European substation is composed of high voltage switch cabinet, mortgage distribution panel, distribution transformer and shell. High voltage is air load switch; transformer is dry transformer or oil-immersed transformer. The box adopts a good heat insulation ventilation structure, beautiful appearance, good heat insulation performance, and the box is equipped with the upper and lower ventilation air duct, the temperature rise caused by the outdoor solar radiation to the transformer room can be reduced to the minimum. The box can be equipped with temperature control forced ventilation device and automatic temperature control device. Each individual unit is equipped with perfect control, protection, live display and lighting systems.
The Number Of LV Main Circuit Design
Main circuit line diagram |
|
|
|
|
classify |
1. Non-compensated monopolar system |
2, there are compensated monopolar system |
3, there is a multi-level compensation system |
4, the knife melt switch simplified system |
Scheme number and description |
102 Second-loop exit line |
202 Second loop exit line |
301 One-plus two-loop exit line |
402 Second-loop exit line |
103 Three-loop exits |
203 Three-loop exit line |
302 Two plus two loop line |
403 Three-loop exits |
|
104 Four-loop exits |
204 Four-loop exits |
303 Two plus three loop exits |
404 Four-loop exit line |
|
105 Five-loop exits |
205 Five-loop exits |
304 Two plus four loop out |
405 Five-loop exits |
|
106 Six-loop exit line |
206 Six-loop exit line |
305 Three plus three loop out |
406 Six-loop exit line |
|
107 Seven-circuit exit lines |
207 Seven circuit exit line |
306 Three plus four loop out |
407 Seven-loop exit line |
|
108 Eight-loop exit line |
208 Eight-circuit exit line |
307 Four plus four loop out |
408 Eight-loop exit line |
|
|
|
308 Five plus five loop out |
409 Nine-loop exit lines |
|
|
|
309 Six plus six-loop exits |
|
|
unit UNIT |
project ITEN |
parameter DATA |
High voltage unit |
Rated frequency of Rated Frequency |
Hz |
50 |
Rated voltage of Rated Vol. |
kV |
6 10 35 |
|
Maximum operating voltage is Max working Vol. |
kV |
6.9 11.5 40.5 |
|
Power frequency withstand voltage of Power Frequency Withstand Vol. |
|
|
|
Ground and alternate / isolation breaks |
kV |
32/36 42/48 95/118 |
|
Lightning impact and voltage resistance Ughining Imputse Withstand Vol. |
|
|
|
Ground and alternate / isolation breaks |
kV |
60/70 75/85 195/215 |
|
Rated current of Rated Current |
A |
400 630 |
|
Rated short-time tolerance current Rated Short Withstanding Current |
kA |
12.5(2S) 16(2S) 20(2S) |
|
Rated peak tolerance current of Rated Peak Withstand Current |
kA |
31.5 40 50 |
|
Low voltage unit |
Rated voltage of Rated Vol. |
V |
380 220 |
Main loop locking current is Main Circuit Rated Current |
A |
100~3200 |
|
Rated short-time tolerance current Rated Short Withstanding Current |
kA |
15 30 50 |
|
Rated peak tolerance current of Rated Peak Withstand Current |
kA |
30 63 110 |
|
Branch current: Branch Current |
A |
10~800 |
|
Number of branch circuits, Circuit Num in Branch |
road |
1~12 |
|
Compensation capacity is Compensution Capacity |
kVar |
0~360 |
|
Transformer unit |
Rated voltage of Rated Capacity |
KVA |
50~2000 |
Short-circuit impedance of Impedonce Vol. |
% |
4~6 |
|
Splitting range is Topping Range |
|
2*2.5% 5% |
|
Linkage group Connection Symbol |
|
Yyn0 Dyn11 |
The Number Of HV Main Circuit Design
Main circuit line diagram |
|
|
|
|
|
classify |
1, the single end without measurement |
2. Single-end band measurement |
3, the ring network without measurement |
4, the ring network belt measurement |
5. Double ends |
Scheme number and description |
11, no charged display |
21, no charged display |
31. No grounding switch at the incoming line end |
41. No grounding switch at the incoming line end |
No charged display, no measurement |
|
|
|
|
|
|
12, with a charged display |
22, there is a live display |
32, the transformer without a grounding switch |
42, the measurement is placed in front of the main switch |
There is a charged display, without measurement |
|
|
|
|
|
|
|
|
Measure in front of the main switch |
33, with three grounding switches |
43, with three grounding switches |
With measurement |
|
|
|
|
|
|
|
|
|
|
|
54, the transformer end without a grounding switch |