YBM Box Substation-American Box Transformer
|
Product characteristics
- Full insulation structure and chain device, to ensure personal safety;
- Fully sealed structure, eradicate the oil quality deterioration, prolong the service life;
- The load switch has the characteristics of three connection, effectively reduces the ferromagnetic resonance;
- Using double fuse protection, to ensure that the system is simple, convenient, economic, reliable and safe operation;
- There are silicon steel sheet core, amorphous alloy core, coil core, etc., low loss, low noise, the box does not heat;
- High voltage inlet line with elbow type cable plug, can be 200A load current, emergency case can be a load switch operation, and has the characteristics of disconnecting switch;
- Small in volume, only about 1 / 3 of the European box change of the same capacity.
General table of combined transformer parameters
rated capacity |
Voltage combination |
Connection group |
Type 9 loss W |
Type 11 loss W |
no-load current |
short-circuit impedance |
noise (db) |
temperature rise (k) |
|||
high-handed |
low pressure |
carrying idler |
load |
carrying idler |
load |
||||||
30 |
6 6.3 10 10.5 11 |
0.4 |
Yyn0 perhaps Dyn11 |
130 |
600 |
100 |
600 |
2.1 |
4 |
55 |
Top 55 The winding 65 |
50 |
170 |
870 |
130 |
870 |
2 |
||||||
63 |
200 |
1040 |
150 |
1040 |
1.9 |
||||||
80 |
250 |
1250 |
180 |
1250 |
1.8 |
||||||
100 |
280 |
1500 |
200 |
1500 |
1.6 |
||||||
125 |
340 |
1800 |
240 |
1800 |
1.5 |
||||||
160 |
400 |
2200 |
290 |
2200 |
1.4 |
||||||
200 |
480 |
2600 |
330 |
2600 |
1.3 |
||||||
250 |
560 |
3050 |
400 |
3050 |
1.2 |
||||||
315 |
670 |
3650 |
480 |
3650 |
1.1 |
||||||
400 |
800 |
4300 |
570 |
4300 |
1 |
||||||
500 |
960 |
5100 |
680 |
5100 |
1 |
||||||
630 |
1200 |
6200 |
810 |
6200 |
0.9 |
4.5 |
|||||
800 |
1400 |
7500 |
980 |
7500 |
0.8 |
||||||
1000 |
1700 |
10300 |
1150 |
10300 |
0.7 |
||||||
1250 |
1950 |
12800 |
1360 |
12800 |
0.6 |
||||||
1600 |
2400 |
14500 |
1640 |
14500 |
0.6 |
Combined type transformer insulation level (combined type transformer dielectric level)
rated voltage |
highest voltage for equipment |
Rated lightning impact withstand voltage (peak value) |
Rated ultra-short-time power frequency withstand voltage (1min) |
|
full wave |
signal carrier |
|||
6 10 |
7.2 12 |
60 75 |
65 85 |
25 35 |
Insulation level of high-voltage electrical components (high-voltage electrical apparatus element dielectric level)
rated voltage |
highest voltage for equipment |
Rated lightning impact withstand voltage (peak value) |
Rated ultra-short-time power frequency withstand voltage (1min) |
||
To the ground and alternate |
isolating fracture |
To the ground and alternate |
isolating fracture |
||
6 10 |
7.2 12 |
60 75 |
70 85 |
32 42 |
|
Insulation level of low-voltage electrical components (low-voltage electrical apparatus element dielectric level)
rated voltage |
60<Ui≤300 |
300<Ui≤600 |
660<Ui≤800 |
800<Ui≤1000 |
Rated ultra-short-time power frequency withstand voltage (lmin) |
2000 |
2500 |
3000 |
3500 |